Dantherm DanX 1-2-3 XD – air handling units
The DanX XD is a very effective ventilation system that uses outdoor air to provide dehumidification using a double heat exchanger that delivers up to a 95% heat recovery. This reduces energy consumption and total operating costs. Making the unit perfect for managing humidity and temperature in the pool room.
Dantherm DanX 1-2-3 XD HP – swimming pool air handling units
|
Dantherm DanX XD diagram
|
Key features
-
Built-in user friendly control system for high-quality demand management. Automatic monitoring and control of pool hall temperature and humidity. The custom-built software runs the unit as efficiently as possible under different conditions.
-
Double crossflow heat exchangers with a high efficiency of more than 85% and a low pressure drop.
-
Built-in bypass for free cooling in summertime.
-
Highly energy-efficient EC plug fans.
-
Efficient M5/ePM10 70% and F7/ePM1 55% compact filters with low pressure drop.
-
Self-bearing cabinet with hot-dip galvanised, powder-painted sandwich panels with 50mm mineral wool insulation, internal partition walls with 30mm and bottom frame with adjustable feet.
-
Designed to withstand the aggressive swimming pool environment (Corrosion class C4 according to EN/ISO 12944-2), with epoxy-coated crossflow heat exchanger, heating coil with aluminium frame, pre-painted fins and epoxy coating to protect all fasteners, bolts, nuts.
-
Two large inspection doors with strong hinges and tongue locks and handles for easy access for service.
-
All-in-one box solutions for easy and quick installation – all sensors and electrical components pre-connected.
-
BMS communication with either Modbus or BACnet.
DanX XD with double cross flow heat exchanger
The DanX XD is a very effective ventilation system that uses outdoor air to provide dehumidification using a double heat exchanger that delivers up to a 95% heat recovery. This reduces energy consumption and total operating costs. Making the unit perfect for managing humidity and temperature in the pool room.
The built-in mixing function takes care not to add any more outdoor air than necessary to provide a comfortable indoor climate. Free cooling is also an option during summer, when the unit can add up to 100% outdoor air into the pool area through a by-pass.
The unit's compact, integrated design enables optimal installation in the technical room. Convenient top or side connections ensure easy access to ducts.
Product specifications
Specifications | Units | DANX 1 XD |
---|---|---|
Nominal air volume |
m³/h
|
1,000
|
Max. air volume |
m³/h
|
1,300
|
Max. external duct pressure |
Pa
|
350
(at nominal air volume)
|
Outdoor air volume |
%
|
0-100
|
Dehumidification capacity VDI 2089 |
kg/h
|
7
(at 30°C/54% indoor)
|
Max. total power consumption |
kW
|
1.1
|
Power supply |
V/Hz
|
230/1ph/50
|
Product size (w x d x h) |
mm
|
1750 x 515 x 1570
|
Weight |
kg
|
254
|
Specifications | Units | DANX 2 XD |
---|---|---|
Nominal air volume |
m³/h
|
1,750
|
Max. air volume |
m³/h
|
2,100
|
Max. external duct pressure |
Pa
|
350
(at nominal air volume)
|
Outdoor air volume |
%
|
0-100
|
Dehumidification capacity VDI 2089 |
kg/h
|
11
(at 30°C/54% indoor)
|
Max. total power consumption |
kW
|
1.2
|
Power supply |
V/Hz
|
400/2ph/50
|
Product size (w x d x h) |
mm
|
1750 x 780 x 1570
|
Weight |
kg
|
344
|
Specifications | Units | DANX 3 XD |
---|---|---|
Nominal air volume |
m³/h
|
2,750
|
Max. air volume |
m³/h
|
3,500
|
Max. external duct pressure |
Pa
|
350
(at nominal air volume)
|
Outdoor air volume |
%
|
0-100
|
Dehumidification capacity VDI 2089 |
kg/h
|
18
(at 30°C/54% indoor)
|
Max. total power consumption |
kW
|
1.9
|
Power supply |
V/Hz
|
400/2ph/50
|
Product size (w x d x h) |
mm
|
2250 x 890 x 1990
|
Weight |
kg
|
465
|