Dantherm TKS 60 – high capacity free cooling unit
High-capacity free cooling
TKS 60 is high-capacity free air cooling designed to control the internal environment of communication shelters using a minimum of energy.
By means of ventilation in an overpressure system, the TKS 60 efficiently removes excess heat from the temperature-sensitive equipment – maintaining the internal temperature within defined limits.
Dantherm TKS 60 – high capacity free cooling unit
|
Key features
-
Total heat management – designed for energy-efficiency with maximum use of controlled ventilation
-
Energy-efficient cooling strategy – automatic change between cooling modes
-
Protect your equipment – standard M5 fine bag filter and optional AirMaze (pat.pend.)
-
Avoid unsceduled service visits – plan service with built-in filter monitor
-
Wide geographical usage – ambient temperature operating range from -25 to 55°C
-
User friendly display for climate control and ethernet and SNMP for remote control
-
Integrated CC3000 control system
Product specifications
Specifications | Units | TKS 60 230V AC |
---|---|---|
Nominal air flow |
m3/h
|
4,200
|
Nominal cooling capacity in W/K (Δt = 1°C) |
W/K
|
1,400
|
Nominal fan power consumption (at 100% fan speed) |
W
|
782
|
Filter class |
|
ePM10 55 % (F5)
|
Fan nominal voltage |
V
|
230V AC
|
Sounds pressure @ 1m |
dB(A)
|
67
|
Controller |
Type
|
CC3000
|
Communication interface |
Type
|
Ethernet SNMP, Modbus
|
Product size (h x w x d) |
mm
|
1100 x 600 x 600
|
Net weight |
kg
|
53
|
Specifications | Units | TKS 60 48V DC |
---|---|---|
Nominal air flow |
m3/h
|
3,200
|
Nominal cooling capacity in W/K (Δt = 1°C) |
W/K
|
1,050
|
Nominal fan power consumption (at 100% fan speed) |
W
|
374
|
Filter class |
|
ePM10 55 % (F5)
|
Fan nominal voltage |
V
|
48 DC (42-57V DC)
|
Sounds pressure @ 1m |
dB(A)
|
64
|
Controller |
Type
|
CC3000
|
Communication interface |
Type
|
Ethernet SNMP, Modbus
|
Product size (h x w x d) |
mm
|
1100 x 600 x 600
|
Net weight |
kg
|
51
|