Calorex DH 150 – condensation dehumidifier
Large-capacity floor-standing dehumidifiers
The DH 150 high-capacity floor-standing commercial dehumidifier is self-contained with fully automatic operation. With an integral humidistat and options for heating, you can be confident in your space being controlled to your needs. A 'constant flow' fan is standard for the DH 150-300, which self-regulates independent on the external pressure loss from ducts, grills, etc. This makes it ideal for warehousing and storage, substations and data centres.
Calorex DH 150 – condensation dehumidifier
|
Calorex DH 150 performance data
|
How to control humidity in data centres
|
Calorex DH 150 installed in large car storage facility
|
Calorex DH 150 Northwood Forestry
|
Calorex DH 150 metal parts storage
|
Key features
-
Self contained with fully automatic operation
-
Integral humidistat
-
Constant flow fan – automatically adjusts to ducting
-
Polyester coated evaporator and condenser
-
Plastisol coated galvanised steel cabinet
-
Hot gas defrost for low temperature operation
-
Reverse cycle defrost for very low temperature operation
Options
-
Return air filter
-
Top discharge box
-
Stainless steel casing
Product specifications
Specifications | Units | DH 150AX |
---|---|---|
Operating temperature range |
°C
|
0-35
|
Dehumidification @ 20°C/60% RH |
l/24h
|
150
|
Heat recovered to air @ 20°C/60% RH |
kW
|
7.4
|
Air flow |
m³/h
|
2,500
|
External static pressure |
Pa
|
0-200
|
Sound pressure level @ 3m |
dB(A)
|
58
|
Power supply |
V/Hz
|
230/1ph/50
|
Nominal power consumption |
kW
|
2.5
|
FLA (electrical) |
A
|
21
|
Maximum supply fuse |
A
|
30
|
LRA (compressor start) |
A
|
61
|
LRA (compressor soft-start) |
A
|
28
|
Heater type |
Optional
|
Top box electric
|
Heat output |
kW
|
9
|
FLA (heater) |
A
|
36
|
Maximum fuse size |
A
|
50
|
R407c gas weight/CO2 equivalent |
kg/t
|
2.50/4.44
|
Product size (w x d x h) |
mm
|
660 x 660 x 1313
|
Weight |
kg
|
130
|
Condensate drain size (flexible plastic hose) |
inch
|
¾ BSPM
|
Specifications | Units | DH 150BX |
---|---|---|
Operating temperature range |
°C
|
0-35
|
Dehumidification @ 20°C/60% RH |
l/24h
|
150
|
Heat recovered to air @ 20°C/60% RH |
kW
|
7.4
|
Air flow |
m³/h
|
2,500
|
External static pressure |
Pa
|
0-200
|
Sound pressure level @ 3m |
dB(A)
|
58
|
Power supply |
V/Hz
|
400/3ph/50
|
Nominal power consumption |
kW
|
2.5
|
FLA (electrical) |
A
|
11
|
Maximum supply fuse |
A
|
16
|
LRA (compressor start) |
A
|
30
|
LRA (compressor soft-start) |
A
|
13
|
Heater type |
Optional
|
Top box electric
|
Heat output |
kW
|
9
|
FLA (heater) |
A
|
12
|
Maximum fuse size |
A
|
16
|
R407c gas weight/CO2 equivalent |
kg/t
|
2.75/4.88
|
Product size (w x d x h) |
mm
|
660 x 660 x1313
|
Weight |
kg
|
130
|
Condensate drain size (flexible plastic hose) |
inch
|
¾ BSPM
|