Dantherm Group
Dantherm

Dantherm AC-M5 MKI – container cooler

Container coolers

The AC-M5 MKI is designed for window mounting in ISO containers. Together with the trap door system the air conditioner is mounted inside the container. It is designed to store within the confinement of the ISO corners of the container during transportation or storage. The AC-M5 MKI is sliding in its trap door system and is deployed from the container for operation. Once deployed the unit is locked from inside the container when operating.

AC-M5 MKI has a fresh-air intake. For applications requiring CBRN/COLPRO compliance, please refer to the AC-M5 MKII product page.

View our range of air cooling units and container coolers suitable for all types of commercial purpose on any scale.

Dantherm AC-M5 MKI – container cooler
Dantherm AC-M5 MKI – container cooler
Dantherm AC-M5 trap door
Dantherm AC-M5 trap door
How to mount the Dantherm AC-M5 container cooler
How to mount the Dantherm AC-M5 container cooler
Dantherm AC-M5 installation
Dantherm AC-M5 installation

Key features

  • Manufactured from hot dip galvanized and powder coated steel sheet
  • Top finish painting is standard NATO green, RAL 6014
  • Air-tight boundary to ambient environment
  • Delivers cooling in ambient temperatures up to +60°C
  • Scroll compressor for high degree of reliability and low noise
  • Two-speed selector for the internal fan
  • “VENT-only” option for ventilation without cooling
  • Stores inside the container during transportation
  • Chosen as the NATO standard, conforming to all NATO requirements and norms
  • All units have unique NATO stock numbers (NSN)

Product Specifications (metric)

SpecificationsUnitsAC-M5 MKI (50 Hz)
Registered NSN number
-
Yes
Operating temperature range, cooling
°C
+20 to +60
Operating temperature range, heating
°C
-32 to +20
Airflow, internal, step I / II
m3/h
420/700
Airflow, fresh air intake, step I / II
m3/h
37/60
Airflow, external
m3/h
1400
Sound level, fan-speed 1 & 2 @ 1m
dB(A)
56 / 62
Protection class
IPX4
Refrigerant
type/kg
R134a/1.4
Global Warning Potential
kW
1430
Max. Cooling capacity
kW
4.9
Cooling capacity @ 55/55°C 30% r.h.
kW
4.6
Cooling capacity @ 35/35°C 30% r.h.
kW
3.6
Heating capacity (optional)
V/Hz
2
Power supply
230/1ph/50
Power supply plug
A
Schuko plug
Max. Amp
A
9.8
Locked rotor amperage (LRA)
kVA
47
Max. power consumption cooling
W
2300
Filter material
PPI 15
Product size (h x l x w)
mm
446 x 752 x 630
Weight net/with trap door system
kg
80 / 95

Product Specifications (imperial)

SpecificationsUnitsAC-M5 MKI (50Hz)
Registered NSN number
Yes
Operating temperature range, cooling
°F
+68 to +122
Operating temperature range, heating
°F
-26 to +68
Air flow, internal, step I/II
CFM
247/412
Airflow, fresh air intake, step I/II
CFM
21/35
Airflow, external
CFM
824
Sound level, fan-speed 1 & 2 @ 3.3 feet
dB(A)
56 / 62
Protection class
NEMA
3R
Refrigerant
type/lbs
R134a/3.1
Global Warning Potential
AR4
1430
Max. Cooling capacity
BTU
16720
Cooling capacity @ 131/131°F 30% r.h.
BTU
15696
Cooling capacity @ 95/95°F 30% r.h.
BTU
12283
Heating capacity (optional
BTU
6824
Power supply
V/Hz
230/1ph/50
Power supply plug
Schuko plug
Max. Amp
A
9.8
Locked rotor amperage (LRA)
A
47
Max. power consumption cooling
W
2300
Filter material
PPI 15
Product size (h x l x w)
"
17.6 x 29.6 x 24.8
Weight net/with trap door system
lbs
176 / 209

Suitable for

  • Camps and field hospitals
  • Military and aerospace