Dantherm Group
Dantherm

Dantherm AC-M18 CBRN – tent cooler

Tent coolers

The AC-M18 CBRN air-conditioner is a portable unit developed primarily to provide air-conditioning in temporary or transportable buildings or tents. The AC-M18 CBRN is a compact, light-weight aluminium unit built into a rigid steel frame. The air-conditioner is designed to operate on COLPRO applications with the evaporator module placed inside the shelter and the condenser module placed outside. The two modules are interconnected by refrigerant hoses and power cables.

The AC-M18 is designed for outside installation with ducted supply and return air. For field hospitals, where the need for filtration is higher than that of normal accommodation, a dual filtration system for the internal air path is available. The ACM 18 is also available as a split system for sealed applications (ACM 18 CBRN).

View our range of air cooling units and tent coolers suitable for all types of application and commercial purpose on any scale.

Dantherm AC-M18 CBRN – tent cooler
Dantherm AC-M18 CBRN – tent cooler
Dantherm AC-M18 CBRN installed in a field hospital
Dantherm AC-M18 CBRN installed in a field hospital
Dantherm AC M18 CBRN installation
Dantherm AC M18 CBRN installation
Dantherm climate solutions for field camps
Dantherm climate solutions for field camps
AC-M air conditioner animation
AC-M air conditioner animation

Key features

  • The AC-M18 is built into a strong metal frame with insulated panels where relevant, powder coated
  • Top finish painting is standard sand colour
  • Scroll compressor for a high degree of reliability and low noise level
  • Automatic phase surveillance
  • Sequential start of units possible
  • HP/LP pressostat switches ensuring long compressor lifetime
  • Fresh air intake
  • Four way fork lift handling
  • Easy strap down on air cargo pallets and stackable (two units on top of each other)

Product specifications

SpecificationsUnitsAC-M18 CBRN (50 Hz)
Registered NSN number
-
Yes
Operating temperature range, cooling
°C
+20 – +60
Operating temperature range, heating
°C
-32 – +20
Air flow
m³/h
2500
Sound level @ 1m
dB(A)
54
Protection class
IP
IPX5
Refrigerant
Type/kg
R134a/3.7
Global Warning Potential
AR4
1430
Nominal cooling capacity
kW
17.5
Heating capacity (optional)
kW
6/16
Power supply
V/Hz
400/3ph/50
Max. running current, cooling/heating
A
18/26
Locked rotor amperage (LRA)
A
73
Max inrush current with soft starter
A
56
Max. power consumption cooling/heating
W
8300/variable
Power cable length
/m
10
Hose connection
Ømm
400
Product size (h x l x w)
mm
(2x) 780 x 725 x 1140
Weight
kg
108/107
SpecificationsUnitsAC-M18 CBRN (60 Hz)
Registered NSN number
-
Yes
Operating temperature range, cooling
°C
+20 – +60
Operating temperature range, heating
°C
-32 – +55
Air flow
m³/h
2500
Sound level @ 1m
dB(A)
59
Protection class
IP
IPX5
Refrigerant
Type/kg
R134a or R513A/4.2
Global Warning Potential
AR4
1430 / 631
Nominal cooling capacity
kW
16.9
Heating capacity (optional)
kW
6/16
Power supply
V/Hz
208/3ph/60
Max. running current, cooling/heating
A
31/48
Locked rotor amperage (LRA)
A
134
Max inrush current with soft starter
A
108
Max. power consumption cooling/heating
W
8300/variable
Power cable length
/m
-
Hose connection
Ømm
400
Product size (h x l x w)
mm
(2x) 780 x 725 x 1140
Weight
kg
112/120

Product specifications (US)

SpecificationsUnitsAC-M18 CBRN (50Hz)
Registered NSN number
-
Yes
Operating temperature range, cooling
°F
68 to 140
Operating temperature range, heating
°F
-26 to 68
Air flow
CFM
1471
Sound level @ 3.3 ft
dB(A)
54
Protection class
NEMA
3R
Refrigerant
Type/lbs
R134a/8.2
Global Warning Potential
AR4
1430
Nominal cooling capacity
BTU
60000
Heating capacity (optional)
BTU
20500/54600
Power supply
V/Hz
400/3ph/50
Max. running current, cooling/heating
A
18/26
Locked rotor amperage (LRA)
A
73
Max inrush current with soft starter
A
56
Max. power consumption cooling/heating
W
8300/variable
Power cable length
ft
32.8
Hose connection
Øin
15.75
Product size (h x l x w)
in
(2x) 30.7 x 28.5 x 44.9
Weight
lbs
238/236
SpecificationsUnitsAC-M18 CBRN (60Hz)
Registered NSN number
-
Yes
Operating temperature range, cooling
°F
68 to 125
Operating temperature range, heating
°F
-26 to 68
Air flow
CFM
1471
Sound level @ 3.3 ft
dB(A)
59
Protection class
NEMA
3R
Refrigerant
Type/lbs
R513A/9.3
Global Warning Potential
AR4
1430 / 631
Nominal cooling capacity
BTU
57665
Heating capacity (optional)
BTU
20500/54600
Power supply
V/Hz
208/3ph/60
Max. running current, cooling/heating
A
31/48
Locked rotor amperage (LRA)
A
134
Max inrush current with soft starter
A
108
Max. power consumption cooling/heating
W
8300/variable
Power cable length
ft
-
Hose connection
Øin
15.75
Product size (h x l x w)
in
(2x) 30.7 x 28.5 x 44.9
Weight
lbs
247/264

Suitable for

  • Camps and field hospitals
  • Events and festivals
  • Military and aerospace