Calorex Delta series – swimming pool air handling units
2-4-6-8-10-12-14-16
The sophisticated Delta air handling units incorporate hybrid heat pump and fresh air dehumidification technology. With dynamic heat recovery to swimming pool water and air using a heat pump, a Delta solution is the ultimate choice for a commercial or public indoor swimming pool.
Calorex Delta – swimming pool air handling units
|
Calorex Delta 10-12-14-16 – swimming pool air handling units
|
How the Delta system works inside a pool hall
|
Calorex Delta 4 front view
|
Calorex Delta 4 side view
|
Calorex Delta 4 back view
|
Delta control home screen
|
Delta control panel settings
|
Calorex Delta set points and switches
|
Calorex Delta home screen plus
|
Key features
-
Dynamic heat pump heat recovery to pool and air
-
Self-regulating fresh air control with heat recovery
-
Automatic control of exhaust air volume to match pool usage
-
Free-cooling (Delta 1-2)
-
Free-cooling and heat pump air cooling (Delta 4-16)
-
Integral LPHW heat exchangers for pool and air
-
Controllable rpm EC/inverter fans in all models
-
PLC control with 5.7" touchscreen user interface
-
Remote monitoring/control
Remote monitoring/control
-
Screen mirroring to Android/iOS mobile devices using third-party app
-
Screen mirroring to web browser with ActiveX
-
BMS interfaces for Modbus, BACnet IP and BACnet MS/TP
-
Wired remote control interfaces
Options
-
Delta 2-6 single or three phase
-
Delta 8-16 three phase only
-
Upgraded LPHW heat exchanger for air heating
-
Left-hand or right-hand orientation (Delta 4-16)
-
Top, side or bottom supply fan outlet
-
Front or rear supply fan outlet (Delta 14-16)
-
Rear exhaust and fresh air connections (Delta 14-16)
Product specifications
Specifications | Units | DT 2 |
---|---|---|
Nominal recirculation air flow |
m³/h
|
2,600
|
Exhaust/fresh air flow (stepped control) |
m³/h
|
130-1,300
|
Total dehumidification @ 28°C/60% RH by heat pump and maximum fresh air |
l/h
|
10.9
|
Heat to air | ||
Via heat pump (Mode B) |
kW
|
4.9
|
Via standard LPHW @ 80°C |
kW
|
22
|
Via upgraded LPHW @ 55°C |
kW
|
19
|
Total Mode B + standard LPHW |
kW
|
26.9
|
Heat to pool water | ||
Via heat pump (Mode A) |
kW
|
5.5
|
Via LPHW @ 80°C |
kW
|
23
|
Via LPHW @ 55°C |
kW
|
11
|
Total Mode A + LPHW |
kW
|
28.5
|
Cooling duty | ||
Total |
kW
|
0
|
Sensible |
kW
|
0
|
Nominal power consumed |
kW
|
2.9
|
R407c gas weight/CO2 equivalent |
kg/t
|
3.0/5.32
|
Width |
mm
|
1740
|
Depth |
mm
|
654
|
Height |
mm
|
1685
|
Weight |
kg
|
310
|
Specifications | Units | DT 4 |
---|---|---|
Nominal recirculation air flow |
m³/h
|
3,000
|
Exhaust/fresh air flow (stepped control) |
m³/h
|
150-1,500
|
Total dehumidification @ 28°C/60% RH by heat pump and maximum fresh air |
l/h
|
12.5
|
Heat to air | ||
Via heat pump (Mode B) |
kW
|
5.1
|
Via standard LPHW @ 80°C |
kW
|
25
|
Via upgraded LPHW @ 55°C |
kW
|
21
|
Total Mode B + standard LPHW |
kW
|
30.1
|
Heat to pool water | ||
Via heat pump (Mode A) |
kW
|
5.8
|
Via LPHW @ 80°C |
kW
|
33
|
Via LPHW @ 55°C |
kW
|
16
|
Total Mode A + LPHW |
kW
|
38.8
|
Cooling duty | ||
Total |
kW
|
-4.2
|
Sensible |
kW
|
-2.9
|
Nominal power consumed |
kW
|
2.9
|
R407c gas weight/CO2 equivalent |
kg/t
|
6.0/10.64
|
Width |
mm
|
1840
|
Depth |
mm
|
704
|
Height |
mm
|
1970
|
Weight |
kg
|
350
|
Specifications | Units | DT 6 |
---|---|---|
Nominal recirculation air flow |
m³/h
|
4,000
|
Exhaust/fresh air flow (stepped control) |
m³/h
|
200-2,000
|
Total dehumidification @ 28°C/60% RH by heat pump and maximum fresh air |
l/h
|
16.6
|
Heat to air | ||
Via heat pump (Mode B) |
kW
|
6.6
|
Via standard LPHW @ 80°C |
kW
|
30
|
Via upgraded LPHW @ 55°C |
kW
|
26
|
Total Mode B + standard LPHW |
kW
|
36.6
|
Heat to pool water | ||
Via heat pump (Mode A) |
kW
|
8.0
|
Via LPHW @ 80°C |
kW
|
33
|
Via LPHW @ 55°C |
kW
|
16
|
Total Mode A + LPHW |
kW
|
41.0
|
Cooling duty | ||
Total |
kW
|
-5.5
|
Sensible |
kW
|
-3.9
|
Nominal power consumed |
kW
|
3.4
|
R407c gas weight/CO2 equivalent |
kg/t
|
7.8/13.84
|
Width |
mm
|
1840
|
Depth |
mm
|
704
|
Height |
mm
|
1970
|
Weight |
kg
|
360
|
Specifications | Units | DT 8 |
---|---|---|
Nominal recirculation air flow |
m³/h
|
5,000
|
Exhaust/fresh air flow (stepped control) |
m³/h
|
250-2,500
|
Total dehumidification @ 28°C/60% RH by heat pump and maximum fresh air |
l/h
|
20.8
|
Heat to air | ||
Via heat pump (Mode B) |
kW
|
8.0
|
Via standard LPHW @ 80°C |
kW
|
35
|
Via upgraded LPHW @ 55°C |
kW
|
30
|
Total Mode B + standard LPHW |
kW
|
43.0
|
Heat to pool water | ||
Via heat pump (Mode A) |
kW
|
10.0
|
Via LPHW @ 80°C |
kW
|
33
|
Via LPHW @ 55°C |
kW
|
16
|
Total Mode A + LPHW |
kW
|
43.0
|
Cooling duty | ||
Total |
kW
|
-6.7
|
Sensible |
kW
|
-4.7
|
Nominal power consumed |
kW
|
4.4
|
R407c gas weight/CO2 equivalent |
kg/t
|
7.8/13.84
|
Width |
mm
|
1840
|
Depth |
mm
|
704
|
Height |
mm
|
1970
|
Weight |
kg
|
370
|
Specifications | Units | DT 10 |
---|---|---|
Nominal recirculation air flow |
m³/h
|
6,000
|
Exhaust/fresh air flow (stepped control) |
m³/h
|
300-3,000
|
Total dehumidification @ 28°C/60% RH by heat pump and maximum fresh air |
l/h
|
25.0
|
Heat to air | ||
Via heat pump (Mode B) |
kW
|
10.0
|
Via standard LPHW @ 80°C |
kW
|
38
|
Via upgraded LPHW @ 55°C |
kW
|
32
|
Total Mode B + standard LPHW |
kW
|
48.0
|
Heat to pool water | ||
Via heat pump (Mode A) |
kW
|
12.5
|
Via LPHW @ 80°C |
kW
|
40
|
Via LPHW @ 55°C |
kW
|
20
|
Total Mode A + LPHW |
kW
|
52.5
|
Cooling duty | ||
Total |
kW
|
-8.4
|
Sensible |
kW
|
-5.9
|
Nominal power consumed |
kW
|
5.9
|
R407c gas weight/CO2 equivalent |
kg/t
|
9.0/15.97
|
Width |
mm
|
1840
|
Depth |
mm
|
854
|
Height |
mm
|
1970
|
Weight |
kg
|
410
|
Specifications | Units | DT 12 |
---|---|---|
Nominal recirculation air flow |
m³/h
|
7,000
|
Exhaust/fresh air flow (stepped control) |
m³/h
|
350-3,500
|
Total dehumidification @ 28°C/60% RH by heat pump and maximum fresh air |
l/h
|
29.2
|
Heat to air | ||
Via heat pump (Mode B) |
kW
|
12.1
|
Via standard LPHW @ 80°C |
kW
|
42
|
Via upgraded LPHW @ 55°C |
kW
|
36
|
Total Mode B + standard LPHW |
kW
|
54.1
|
Heat to pool water | ||
Via heat pump (Mode A) |
kW
|
15.0
|
Via LPHW @ 80°C |
kW
|
40
|
Via LPHW @ 55°C |
kW
|
20
|
Total Mode A + LPHW |
kW
|
55.0
|
Cooling duty | ||
Total |
kW
|
-10.1
|
Sensible |
kW
|
-7.1
|
Nominal power consumed |
kW
|
7.4
|
R407c gas weight/CO2 equivalent |
kg/t
|
8.0/14.19
|
Width |
mm
|
1840
|
Depth |
mm
|
854
|
Height |
mm
|
1970
|
Weight |
kg
|
460
|
Specifications | Units | DT 14 |
---|---|---|
Nominal recirculation air flow |
m³/h
|
10,000
|
Exhaust/fresh air flow (stepped control) |
m³/h
|
670-6,700
|
Total dehumidification @ 28°C/60% RH by heat pump and maximum fresh air |
l/h
|
56.5
|
Heat to air | ||
Via heat pump (Mode B) |
kW
|
30.0
|
Via standard LPHW @ 80°C |
kW
|
85
|
Via upgraded LPHW @ 55°C |
kW
|
72
|
Total Mode B + standard LPHW |
kW
|
115.0
|
Heat to pool water | ||
Via heat pump (Mode A) |
kW
|
35.0
|
Via LPHW @ 80°C |
kW
|
65
|
Via LPHW @ 55°C |
kW
|
32
|
Total Mode A + LPHW |
kW
|
100.0
|
Cooling duty | ||
Total |
kW
|
-23.0
|
Sensible |
kW
|
-13.0
|
Nominal power consumed |
kW
|
12.3
|
R407c gas weight/CO2 equivalent |
kg/t
|
21.5/38.14
|
Width |
mm
|
2860
|
Depth |
mm
|
1126
|
Height |
mm
|
2120
|
Weight |
kg
|
954
|
Specifications | Units | DT 16 |
---|---|---|
Nominal recirculation air flow |
m³/h
|
12,000
|
Exhaust/fresh air flow (stepped control) |
m³/h
|
850-8,000
|
Total dehumidification @ 28°C/60% RH by heat pump and maximum fresh air |
l/h
|
62.4
|
Heat to air | ||
Via heat pump (Mode B) |
kW
|
35.0
|
Via standard LPHW @ 80°C |
kW
|
90
|
Via upgraded LPHW @ 55°C |
kW
|
77
|
Total Mode B + standard LPHW |
kW
|
125.0
|
Heat to pool water | ||
Via heat pump (Mode A) |
kW
|
43.0
|
Via LPHW @ 80°C |
kW
|
65
|
Via LPHW @ 55°C |
kW
|
32
|
Total Mode A + LPHW |
kW
|
108.0
|
Cooling duty | ||
Total |
kW
|
-28.0
|
Sensible |
kW
|
-15.0
|
Nominal power consumed |
kW
|
17.0
|
R407c gas weight/CO2 equivalent |
kg/t
|
21.5/38.14
|
Width |
mm
|
2860
|
Depth |
mm
|
1126
|
Height |
mm
|
2120
|
Weight |
kg
|
1020
|